About This Readme

This Readme provides information about Wonderware® Historian 2017 (version 17.0.18000).

For information about using the product, see the Wonderware Historian documentation.

New Features In This Release

The Wonderware Historian 2017 (version 17.0.18000) release includes these features:

  • Updates for Wonderware Historian InSight
    This version these new InSight features:
    • Dashboard enhancements (customization and auto-refresh
    • Ability to plot discrete tags
    • Pan and zoom in line charts
    • Multi-axis and stacked tags mode in line charts
  • Enhanced auto-summary system
    Provides fast data retrieval, even for long data periods
  • Alarm and Events replication
    This version includes replication support to on-premises tier-2 servers or Wonderware Online InSight.
  • Cyber-security improvements in reducing Admin privileges needs
  • Support for Historian using a SQL Server instance
  • A new Schneider Electric licensing infrastructure
    Licensing is now server-based. A centralized license management system offers license server auto-detection and configuration for servers running Wonderware Historian 2017.

Known Issues

  • For servers running Wonderware Historian 2008 R2 or 2012 R2, InSight browser will not work properly if Internet Explorer Enhanced security is enabled on the server. For these configurations, you must use the Server Manager console to disabled IE's Enhanced security.
  • Some charts are not drawn for complete time range if that range includes both daylight savings and standard times.

Resolved Issues In This Release

This section describes issues that have been resolved in Wonderware Historian version 17.0.18000.

These issues are listed by their Change Request (CR) number and any assigned Service Request (SR) number. The left column of the table shows the original Change Request in which the issue was identified. The Related Change Requests column lists other change requests that are related to the original change request.

Original Change Request

Related Change Requests

Description

L00135973

L00137532,
L00144021,
L00144104

SR 49410191, SR 49410040: "Administrators" group share permissions exist on InSQL8SF$ share name.

L00140741

L00141226,
L00141795

SR 103141118: (aahIOSvrSvc) When a tag is added that doesn't exist, every tag after that will have bad quality.

L00140841

L00144160

SR 49810065: When using the Alarm system, an issue exists with AlarmDuration field.

L00140969

L00144161

SR 34114189: A query that uses Daylight Saving Time results in an error

L00141025

 L00142313

SR 103141718, SR 10917557: ClientAccessPoint leaks memory for ExecuteSqlStatement calls.

L00141226

L00144299

SR 103140340: When a tag from InTouch (via aahiosvrscv ) that didn't previously exist in Historian is received, evey good tag added after that is marked as having bad quality.

L00141394

 L00143988

SR 192112147: Historian Data Importer crashes during the data import.

L00141495

L00141767,
L00142112

SR 103140601: Incorrect values for Query or Trend for "Latest" data after upgrade to 2014 R2 SP1.

L00141426

 

SR 37511227: Tag search is inconsistent in Wonderware Historian InSight (on-premises).

L00141506

 

SR 50410723: Search Index Translog file grew to 20G, causing Historian to stop collecting data.

L00141611

 

SR 51511796: Unable to access to Historian Online via OData interface after upgrading to SP2014R2SP1P01.

L00141649

 

SR 37511215: Counter query returns inconsistent data when timeframe changes

L00142080

 

SR 51311709: Two warnings showing up once per hour. Both include this text: "Main Metadata Server failed to copy...; last error = 80 (The file exists)".

L00142231

L00142489,
L00142599

SR 51311862, SR 103141794: A huge amount of memory consumption occurred for aahEventStorage.exe services.

L00142287

L00144218

SR 103141346: When a customer changes an event tag configuration, the event history sends the wrong email messages.

L00142298

 L00143588

SR 54810238, SR 103143174: Warning messages are displayed in the logger: GetNextDataQueryResult failed (79;"Date and Time" --> <INFINITY>... error = 51 (Unknown client)

L00142674

 

Historian should support Min/Max Raw and Min/Max EU where the "min" is greater than the "max"

L00142820

 

SR 10917696: OData query returning duplicate tagname records.

L00142935

L00144145,
L00144146,
L00144090,
L00144091

SR 48911529: When the Alarm DB Logger Manager isn't used, historical alarms from Application Server don't have the "Tagname" field populated with the object name that generated the alarm.

L00143133

 

SR 48911458: While trying to run a query, the "GetNextDataQueryResult failed" warning posts to the SMC log and query fails.

L00143230

 

SR 103142952: Installing the patch Historian Search (64 bit) fails and returns code 1603.

L00143237

 

SR 103142832: (A2ALMDB) Some alarms regarding AlarmState are written in wrong order.

L00143436

 

SR 103143213: v_AlarmHistory supports only a single "like" comparison.

L00143664

 L00142523

SR 103140324: A racing issue occurs while creating the server storage node.

L00144023

 

SR 103143833: A constant growth of handles and the private memory set occurs on dnx. exe.

L00144228

 

SR 19714377: Tier-2 value of One Minute (1M) replicated analog tags is one value behind the current tier-1 value.