Release Notes For InTouch Machine Edition

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 6 (Friday, June 26, 2015)

ID Type Description
1329 Issue Modified the Windows CE runtime to properly handle touch screen events and reset the NoInputTime function
1720 Issue Modified the X-Ref to search for tags stored in the Event Logger
2854 Issue Resolved issue with the Alarm Control object not properly sorting its contents by the "Messages" column
3079 Issue Resolved issue with the translation of the word "Duration" on the Trend Control object returning to the original language when switching between screens
3386 Issue Resolved issue with the recipes not reading the XML files that did not have line break between the XML tags
3427 Issue Resolved issue with Alarm not being acknowledged on the Alarm Control object by double-clicking on one of the Custom Field Columns
5207 Issue Resolved issue with the Column width for Alarm Object Custom Fields
5302 Issue Resolved issue with Grid object having Data Source as Class Tags not working as it used to in previous versions
6772 Issue Resolved issue with a combination of modifier keys, such as Ctrl, Alt, Shift, and another keys, not executing the commands configured on the OnUp scripts when the modifier keys were being released first
6838 Issue Resolved issue with Tag Integration not being able to properly synchronize class members to Structure and UDTs that were modified.
7357 Issue Resolved issue with the Trend Control object, that when clicking on the "Cancel Zoom" command, the pen line on the Trend chart was sometimes being plotted in random places
7488 Issue Modified the PrintWindow() function to no longer allow the user to try to print on the StudioPDF printer, which would cause the system to not work properly
7495 Issue Modified how linked symbols are saved in a project: when you paste a linked symbol into a screen, the symbol file will be copied to the project's Symbol folder if it is not already there. If that same symbol is already there, identical, and with the same name, the newly pasted symbol will link to the same file, otherwise, the user will be prompted if the new symbol should replace the existing one or not
8423 Issue Resolved issues related to the Mobile Access feature when there were multiple simultaneous connections and disconnections.
8487 Issue Resolved issue with the Secure Viewer and Web Thin Client taking twice the time configured to switch stations to completely connect to the second server when having server tags on the screen that is open
8491 Issue Resolved issue with the Tag Integration for Rockwell PLC5/SLC500 using too much memory and processor
8588 Issue Fixed problems to run the Fluke DAQ application.
8676 Issue Linked symbols that contain linked pictures will be properly compared when pasted to an application avoiding unnecessary overwrite operations.
8697 Issue Resolved leak of memory issue with the OPC Server module that was happening with some specific calls from OPC Clients
8777 Issue Resolved issue when opening a screen with mnemonics and class tags, on the Min and Max of the dynamic properties, such as bargraph, text, text box, position, rotate, size
8786 Issue Resolved issue with the Grid Control not working properly when switching the Date format using the SetDateFormat function on the Viewer module
8799 Issue Resolved issue with sending alarms via Email, having more Custom Fields enabled than what was actually configured on the Alarm Worksheet, that would cause the system to become unstable
8842 Issue Resolved issue with the Trend Annotation not working properly after executing the SetDateFormat() function on the Viewer Module
8848 Issue Modified the Trend Control object to update the Date Format on the X axis after the SetDateFormat() is executed
8865 Issue Resolved issue with the E-sign not working properly on Secure Viewer after disconnecting from the server and reconnecting to it.
8874 Issue Resolved issue with the ShowInplaceInput() function ignoring the following parameters: numStartXPos, numStartYPos, optNumEnablePasswordMode.
8877 Issue Resolved issue with the "Insert Copied Cells" command not working properly when used in the worksheet's blank cells replacing existing rows.
8878 Issue Resolved issue with the Text object with the Dynamic Position property, when the SetLanguage() function was being called, it would cause the translated text object to return to its original position until the Position value change or the screen is reopened
8885 Issue Optimized the initialization of the Trend Worksheets when configured to communicate with the Wonderware Historian. Before this change, the Studio Database Gateway (StADOSvr.exe) would take too long to initialize and would cause a timeout with the runtime.
8890 Issue Modified the Database Interface Trace messages on the store and forward capability to display local time instead of UTC.
8891 Issue Modified the OPC Client modules (both the OPC DA 2.05 and the OPC XML/DA modules) to update the studio tag properties (TimeStamp and/or Quality) when receiving a message from the OPC Server, even if the tag value does not change.
8900 Issue Resolved issue with the Security System causing the user to lose its privileges when switching screens, in very specific situations, when running in LDAP mode
9012 Issue Resolved issue with the "Verify" command displaying message related to the Security System, even though the Security System was disabled, in some specific projects
9129 Issue Resolved issue with the Grid object not allowing the user to properly scroll through the rows once one of them was selected
9153 Issue Resolved issue with the OPC Server not runing as a Service if you configure the service to run with a user different than the one that is current logged on
9158 Issue Resolved issue with "Remove unused tags" functionality trying to remove class array tags that are actually being used in the projects when their indexes are VBScript variables
9191 Issue Resolved issue with the Trend Control having some points disappearing when it was in Run Mode and displayed on Web Thin Clients
9219 Issue Modified the EmbeddedView to run on devices where the image does not contain the basic c++ libraries.
9230 Issue Resolved issue with the Viewer displaying the background bitmap even after the user disabled it
9240 Issue Resolved issue with the TCP/IP Server task not being automatically enabled when saving screens as HTML for the first time, like it used to do
9315 Issue Resolved issue with the Trend Control not showing data properly when the database was configured to use Local Time + Time Difference
9328 Issue Resolved issue with the Development Environment turning very slow after some time due to temporary files being created
9332 Issue Resolved issue with the Security System not working properly in Distributed Mode when there were several Distributed Remote clients connected to that same server
9381 Issue Modified the Mobile Access Script Engine to properly handle cases where with a MsgBox call containing spaces before the parenthesis. Before this modification, screens containing expressions such as 'MsgBox ("Test" )' would fail to load.
9456 Issue Resolved issue on Windows Embedded (both Compact and Standard) with the Trend task having errors when trying to store to a database tags with bad quality
9518 Issue Resolved issue with the Scan configuration not working properly when the option "Screen" was selected on the Driver, OPC DA 2.05, OPC UA Client and OPC XML-DA runtime tasks
9565 Issue Resolved issue with the Filecopy function not working properly when the destination parameter is only the path, without the file name, and the user does not configure the optTimeout parameter
9570 Issue Resolved issue with the Tab Order on a screen being overwritten if an object had a dynamic property associated to it
9574 Issue Implemented a new feature to save the Security System information every 5 minutes, to avoid that changes made during the runtime to be lost in case of an unexpectedly system failure.
9768 Issue Resolved issue with class member replace function not replacing the tag members properly in projects with arrays in scripts that were using VBScript variables as indexes.
9770 Issue Fixed the Wonderware Historian to properly parse strings in curly brackets for the Trend Task when using database.
9819 Issue Resolved issue with files being removed from the project when other applications, such as back up and anti-viruses, were locking these files at the same time that we were trying to write to them
9852 Issue Modified the Trend Control object to allow the user to use the Window Zoom to include the scale limits on the selection
9853 Issue Modified the Popup Input window to show the same value as the Text Object that called it when it is open
9854 Issue Fixed the grid control to properly print or send to PDF files when using the multiline option.
9873 Issue Resolved issue with the FindFile function no longer working properly when using the optTimeout parameter
9877 Issue The TagsDBGetAlarm function can now handle the maximum message alarm size.
9887 Issue Resolved errors when trying to open corrupted screen files
9982 Issue Resolve Tabulation issue with the Text Box control on Web Thin Clients
9990 Issue Resolved issue with Multi-touch functionality becoming unstable in certain specific situations
10014 Issue Resolved an issue with the Tag Integration for RSLogix 5000 where it did not properly import some array tags.
10017 Issue Resolved issue with the "Verify" command causing the system to be unstable when there were corrupted screen files on the project.
10217 Issue Resolved issues with the Trend Control not properly drawing the lines and having issues when scrolling through the period of time during the Daylight Saving change
7372 Change Request Created a new log message that is displayed on the Output Window and LogWin when the Auto LogOff is executed
8335 Change Request Modified the Mobile Access Tabular to be registered as the Launching User
8465 Change Request Changed the Security System AES initialization to prevent corrupting the Security System files
8614 Change Request Enhanced the Tag Integration for Schneider Unity Modbus to support %M addresses and for tags declared as DWORD.
9114 Change Request Modified E-Signature window to do not grayout the User Name field by default when the timeout value has not been elapsed
9984 Change Request Modified Security System in LDAP mode to use a different ping implementation
9993 Change Request Enhanced the Tag Integration with TwinCAT to support online retrieval of the variables configured in a runtime PLC instance.
7820 Requirement Improved the Tag Integration for the TwinCAT provider to support TMC and TMI files.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 5 (Friday, March 20, 2015)

ID Type Description
5671 Issue Modified OPC UA Client to display an error message in the log when communicating with unsupported items
5987 Issue When deleting a screen using the Project Explorer treeview, now all the files related to that screen that were saved on the Project’s Web folder, such as the html, scc and ssma files are also deleted
6268 Issue Resolved issue with the Trend Control object not working properly when using the Local Time + Time Difference option to save the data on the Trend worksheet
6938 Issue Modified the Mobile Access to prevent memory leaks when connecting and disconnecting clients. A small leak would eventually make the Mobile Access stop responding. In order to restore the user would have to reset the IIS application pool.
7362 Issue Resolved issue where the Visibility property was not working properly with ActiveX objects
7511 Issue Resolved issue with the Hardkey license not working properly when some other software packages such as Rockwell Studio5000 and Codesys v3.5 were installed on the same computer
7584 Issue Resolved issue with the Tag Integration for RSLogix not working properly when some L5K files contained several levels of nested UDT
7725 Issue Resolved issue with the Screen Scripts Screen_OnOpen and Screen_OnClose procedures, that were sometimes being executed incorrectly on a startup screen when it was being reloaded.
7882 Issue Resolved issue with the Trend Control not properly handling the pens and duration after zoom was being used, and the user closed and reopened the screen that had that object, causing invalid values to be loaded on the limits and duration
7883 Issue Resolved issue with the Trend Control object not properly drawing the pens when scrolling back and forth, when the Data Source is MS Access with a large amount of data saved
7884 Issue Resolved issue where the Virtual Keyboard was being opened in unusable places in the screen
7909 Issue Fixed a problem in Mobile Access where modifying a tag continuously (i.e.: Screen OnWhile logic) on the client would make the client stop receiving updates on the server.
7911 Issue Resolved issue with the Remote LogWin causing errors in certain projects running on Windows Embedded Standard 7
7913 Issue Resolved issue with RSLogix5000 Tag Integration when the L5K file had strings created with a certain number of characters as value causing a line feed
7956 Issue Resolved issue with deleting rows from worksheets after sorting by the Tag Name column
8023 Issue Resolved issue with the custom Watch Dog tag for the Secure Viewer Thin Client not working properly in redundant mode
8031 Issue Resolved issue with the HST2TXT function causing errors when the date format in the Thin Clients and the Server are different.
8043 Issue Modified the OPC UA Client to properly handle invalid configuration files.
8046 Issue Resolved issue where the “Test Screen” feature was enabling the background color on Text objects having the Text Data Link property and the Input enabled
8125 Issue Resolved issue with the built-in IF() function not working properly when it had mnemonics on the parameters, and when running specifically on WinCE devices, ARMV4I platform
8132 Issue Modified the EmbeddedView run-time to remove the requirement of having the C++ libraries in the embedded device image
8198 Issue Resolved an issue that was happening when we tried to close certain screens that were already invalid
8216 Issue Resolved issue with EmbeddedView OPC DA Client not properly handling TimeStamp values received from the OPC Servers
8242 Issue Resolved issue with the Remote Agent (CEServer.exe) not recognizing Hardkeys on Windows Embedded Compact (CE) and Windows Embedded devices with a brand new installation
8290 Issue Resolved issue with the StrFromTime() function not working as described in the documentation.
8331 Issue Modified the Mobile Access to properly evaluate the security level at the Main (root) node.
8441 Issue Resolved issue with the Class members editor that was allowing the user to create class members with invalid characters
8502 Issue Modified the OPC UA Client to properly check for good qualities. When receiving good quality different from OpcUa_Good the OPC UA Client was reporting them as bad quality..
8507 Issue Resolved issue with the FileCopy() function returning an error if source file has the read-only attribute set, even with the file being properly copied, when if you configure any value on the last parameter optNumTimeOut
8559 Issue The Viewer does not leak memory when switching screens with tags inside rectangles.
8575 Issue Modified Mobile Access to support access to the server through a router without having to configure the Web.Config file
8587 Issue Resolved memory allocation issue with the Text Box Control object
8589 Issue Resolved issue in the StudioToolkitNET with the UNTranslateEX function
8619 Issue Tag Integration: Resolved issue to enforce that all tags are properly mapped (between Studio and TwinCAT), even after modifying the configuration of structures (classes) in the TwinCAT program (e.g.: adding or removing members)
8649 Issue Resolved issue with the event logger feature not logging the first log on action on a Web Thin Client
9219 Issue Modified the EmbeddedView to run on devices where the image does not contain the basic c++ libraries.
8111 Change Request Enhanced the Register module to make the selected network card persistent when using Softkey and opening the “Settings” window.
8325 Change Request Implemented a new capability to dynamically change the Screen Background Image using {Tag} on the “Shared image” field of the Screen Attributes window
8332 Change Request Modified the way that passwords are saved on screen files when protecting them with passwords.
8607 Change Request Created new configuration in the app file to deny blank passwords when using the Security System in LDAP mode
8731 Change Request Increased the length of the string that can be entered on the LDAP Query Filter configuration
9028 Change Request The following entry in the "ApplicationName.APP" file has been created to disable a background thread for the LDAP connection, which may result in inconsistent results from certain LDAP Servers: Section [Options], parameter "EnableThreadLDAP=0"

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 4 (Thursday, December 18, 2014)

ID Type Description
4944 Change Request Implemented new Data protection feature to encrypt sensitive information
5188 Change Request Improved Trend Control to allow 'Cancel Window Zoom' if the user stops and re-runs during the runtime.
6612 Change Request Modified the Translation feature to no longer automatically import some of the Data from the Database configurations on screen control objects connected to Databases, such as Grid Control, Trend Control and Combo Box
7239 Change Request Modified the GetHardkeySN() function to properly return the updated value when removing or replacing the Hardkey after starting the application
4945 Requirement Modified the way the encrypted data is exchanged
7353 Requirement Enabled the ShowMessageBox function to work also when called by a Background Task
5954 Issue Resolved issue with a a buffer overflow being generated when reading a corrupted screen
6395 Issue Resolved issue with some parameters of the Trend Control object not working properly when using the Open() function and mnemonics
6493 Issue Resolved issue with using a String Tag on the Trend Control Duration field and zooming in, out and cancelling zoom not properly rounding the values
6506 Issue Resolved issue with GetAppPath() function returning a value with 2 backslashes at the end after the project has been downloaded to a Window PC target system
6613 Issue Resolved issue when using the Portuguese MUI and not being possible to see the correct number of tags on the text field on the lower right corner of the Development Environment that shows the tag count
6652 Issue Modified the Mobile Access to support iOS8
6655 Issue Resolved issue with PanelBuilder Import wizard creating an invalid scheduler worksheet when importing projects without a tag assigned to the screen number
6656 Issue Modified the mobile access to support screen name with space when specifying the screen name in the query string (e.g.: http://localhost/ma?screen=Screen%20With%20Space)
6773 Issue Enhanced the login page to display more precise information when the logon fails.
6803 Issue Fixed problem with functions GetTagValue and SetTagValue for Mobile Access. The functions were not working properly if the TimeStamp field was part of the tag name specified e.g.: GetTagValue( Tag->TimeStamp ).
6808 Issue Resolved issue with the Collaboration Tool not properly handling the Email information saved on the Alarm worksheets
6977 Issue Resolved issue with the Trend Control object where the Cursor Output Value, in certain situations, was displaying a wrong value when the screen having this object was first open
7038 Issue Resolved issue with the print orientation not working properly when printing using the trigger on the Grid Control object
7179 Issue Fixed system error on Mobile Access when loading several clients simultaneously.
7210 Issue Modified the dialogs of certain objects on the Web Thin Client to no longer have the “Close” system menu, no longer be able to drag them and do not allow right clicking on them
7221 Issue Resolved issue with the Mobile Access that, on certain situations, when saving screens, the font object was being set to an invalid value.
7238 Issue Resolved issue with the Date and Time functions not returning the correct values depending on the Daylight Saving status and parameters
7293 Issue Resolved issue with Secure Viewer connected to redundant servers having issues when switching servers
7374 Issue Modified the Mobile Access to display '????' in the tag value when an invalid tag or an invalid array index is specified. Prior to this change Mobile Access would display System.Object
7380 Issue Fixed an issue with Mobile Access VBScript parser where function calls receiving array tag(s) as parameter(s) would not work as expected.
7430 Issue Resolved issue with the Auto-LogOff feature not working properly when the Security System is configured to LDAP mode
7440 Issue Resolved issue with the SetLanguage function causing errors on the TCP/IP Server task when called simultaneously from different Thin Clients
7458 Issue Resolved issue with the modifier keys causing commands configured on the “On Up” action of the Command animation to be executed
7465 Issue Resolved issue with Remote Management not being able to connect to PocketPC in ActiveSync mode
7504 Issue Resolved issue with the Security System, when switching between LDAP and Local modes, and restarting the software, causing the LDAP settings not to be retained
7522 Issue Resolved issue errors that were happening when we tried to close certain screens that were already invalid
7646 Issue Resolved issue with the SNMP agent not working properly
7747 Issue Resolved issue with Secure Viewer not displaying Linked Pictures addressed with absolute paths

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 3 + Hotfix 2 (Wednesday, November 12, 2014)

ID Type Description
7458 Issue Resolved issue with the command animation, that when pressing and releasing one of the modifier keys (i.e. Ctrl, Alt, Shift), during the Runtime, could cause the commands configured on the “On Up” action to be executed even if they were not associated to keyboard shortcuts.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 3 (Tuesday, October 28, 2014)

ID Type Description
3696 Requirement Implemented Tag Integration interface for the AutomationDirect DoMore PLC Family.
5394 Requirement Enhanced the Mobile Access solution to support the Security System Auto LogOff feature
5859 Requirement Added support for General alarm fields for the TagsDBSetAlarm and TagsDBGetAlarm functions
5998 Requirement Implemented capability to customize the Viewer icon on the Task Bar.
6061 Requirement Created a new built-in function, GetLastESignUser(), that returns the name of the user authenticated to execute a screen Command (animation) with E-signature
6262 Requirement COSYS Tag Integration: added ARTI3 support
4713 Issue Resolved issue with the translation feature not working on the Combo Box object when using data source as Database
4726 Issue Changed the way Development Environment handles the Fill Effects for rectangles when the system is targeted for an Embedded runtime
5032 Issue Resolved issue with the Import Wizard Tags Filter Dialog not working for any language other than English
5166 Issue Resolved issue with Remote Management, when connectign to a EmbeddedView system, if your target folder is not a Subfolder of the Remote Agent (CEServer), the selected target folder is not kept
5299 Issue Resolved issue with the Text Data Link dynamic property not being updated when the Screen Attribute parameter Hide screen instead of closing it was checked
5330 Issue Resolved an issue where an incorrect message was displayed when the project developer tried to insert the same System Symbol more than once.
5376 Issue Resolved issue with the Ctrl+F Find functionality ignoring the last row on any worksheet on the development environment, such as Driver, Scheduler, Math, and so forth
5616 Issue Modified the Protection Manager to allow you to select a MAC address when you change your softkey license. This is necessary because the license's site code is based on the computer's MAC address, and the computer may have more than one MAC address if it is connected to a VPN or otherwise using a virtual NIC at the time that you change your license.
5652 Issue Fixed a problem with the OPC DA 2.05 worksheet where the Div column would display a wrong label.
5666 Issue Resolved issue with the popup input for text object not being properly displayed when more than one monitor was being used
5804 Issue Resolved issue with Remote Management experiencing timeout problems when downloading projects to remote computers when the Remote Agent is configured with users and passwords on its Security System
5871 Issue Resolved issue with the Trend Control object when enabling the Advanced-> Auto Save option, it would cause some tags configured in the fields to not work properly
5884 Issue Resolved an issue where the built-in function TagsDBAddTag would not accept new tag names beginning with the "@" character.
5910 Issue Modified the OPC XML/DA to properly set the quality of the tags to BAD when the client fails to connect to the server.
5939 Issue Resolved issue with the Output Window and LogWin module no longer showing Database messages that would include important information such as wrong table or column names when using the Grid Control
5946 Issue Resolved issue with the Trend Control object not accepting mnemonics on the Axes->Duration field
5976 Issue Resolved issue where opening the “Config” window of the Command property Object Properties, and clicking on the “Cancel” button, would delete the VBScript configured on it
5978 Issue Resolved issue with Alarm Control not being able to properly use the Filter Expression when it had Custom fields containing lower case characters or when the last Custom field was being used
5987 Issue When deleting a screen using the Project Explorer treeview, now all the files related to that screen that were saved on the Project’s Web folder, such as the html, scc and ssma files are also deleted
5997 Issue Resolved issue with the Report task not working properly when some Asian characters were used
5999 Issue Resolved issue with the capability to save the alarm state whem the alarm is generated by the Driver and/or OPC, the alarm selected tag showed a string in the format #:#:#:# instead of the tag name.
6009 Issue Resolved issue with the tag not having its value properly displayed on some specific screen objects with animations.
6059 Issue Modified the built-in RunGlobalProcedureOnTrigger() function to work also when called from a Secure Viewer Thin Client
6060 Issue Resolved issue with the Security System when using Tags in the “Password Aging” and/or in the “E-signature timeout” fields from “Security System > Groups > [GroupName] > Advanced” dialog being reset to their “lowest value after running the application” when executing GetUserFullName()
6095 Issue Resolved issue with the Remote Management tool not allowing the user to select a non-empty folder as your target application when browsing for a target folder in the development environment
6107 Issue Modified the Database Functions to display an error message on the log when the maximum number of connections with the database is exceeded.
6140 Issue Resolved issue with the Virtual Keyboard not being properly placed when the user had more than one monitor
6167 Issue Resolved issue where it was not possible to configure mnemonics on the Trend Control > Axes > Duration field, even though we could configure a tag on the same field
6185 Issue Resolved issue with using the Print button on the Trend Control object was not printing values on the SPC columns when they are configured to be displayed (Min, Max, Avg, etc...)
6314 Issue Resolved issue with key combinations on the Command animation not working on the OnUp scripts when one of the keys was being released first
6325 Issue Modified the Mobile Access scripting engine to properly handle line breaks and user functions with suffix MsgBox.
6432 Issue Resolved issue with the X-Ref tool wrongly showing that the tags would be present in certain documents where they were not
6453 Issue Resolved issue with the Trend Control using Data Source as Text and the X-Axis containing Date/Time information
6522 Issue Resolved issue with the Mobile Access interface where the Mobile Access Client would stop receiving tag changes from the server.
6582 Issue Modified the Mobile Access to prevent fatal error when closing a screen with Combo Box before the Combo Box can load its data.
6792 Issue Resolved issue with security system in distributed mode causing the TCP/IP server task to create unnecessary connections.
7458 Issue Resolved issue with the command animation, that when pressing and releasing one of the modifier keys (i.e. Ctrl, Alt, Shift), during the Runtime, could cause the commands configured on the “On Up” action to be executed even if they were not associated to keyboard shortcuts.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 2 (Friday, August 08, 2014)

ID Type Description
2872 Requirement Modified the Trend task to make it easier to troubleshoot when historical data are not saved correctly.
3316 Change Request Modified the message that is displayed when the project developer clicks "Trust server certificate" in the security settings for an OPC UA connection (OPC UA > Connections > Server Configuration > Security), in order to warn them when the certificate is self-signed.
4994 Change Request Implemented the new built-in functions TranslationLookupLoad, TranslationLookupGet, and TranslationLookupClose, which allow the project developer to create lookup maps between different languages. For more information, see the documentation.
4995 Change Request Improved the ADO.NET database gateway (StADOSvr) to make it possible to specify a locale (i.e., language and country) for database queries, rather than use the locale that is specified in the host's system settings.
5685 Change Request Modified the built-in function CheckESign to take a security access level as an optional parameter. Previously, the function would validate against level 0, and level 0 is still the default, but this parameter allows the project developer to specify any level.
3989 Issue Resolved an issue with Linked Symbols that are configured to use Class tags imported via tag integration.
4025 Issue Resolved an issue with the built-in function FileWrite, where it did not properly handle the Visual Basic CRLF character (vbCrLf).
4372 Issue Modified the built-in function SetViewerPos to be able to take negative values as parameters. This is to make it easier to manage the Viewer on multiple monitors.
4461 Issue Resolved an issue with the Smart Message object not displaying the last configured message.
4545 Issue Modified the interface between the development station and the target station in order to avoid errors when using the "Get From Target" command (Remote Management > Import) to import projects from the target station.
4903 Issue Resolved issues with Runtime for Windows Embedded Compact not properly interacting with SQL CE 3.5.
5059 Issue Resolved an issue with the project security system where, if a project had been running for extended period (i.e., more than one week), creating a new user would generate errors.
5064 Issue Resolved an issue where the OPC UA Client task would sometimes crash if it attempted a read/write operation while it was disconnected from the OPC UA server.
5092 Issue Modified the ADO.NET database gateway (StADOSvr) to work even if Microsoft .NET Framework 4 is not installed on the computer that hosts the gateway. .NET Framework 4 became a requirement when support for Wonderware Historian was implemented in a previous release (see item 3423). This modification ensures that the gateway will continue to work for most database connections, but if you plan to connect to a Historian database, .NET Framework 4 is still required. For more information, see the documentation.
5099 Issue Resolved an issue with the EmbeddedView runtime where it did not show the window menus (File, Security, Tools) even if it was configured to do so (Project Settings > Viewer).
5185 Issue Resolved an issue where the "Test Screen" command would change the background color of Text objects that have the Text Data Link animation applied to them. (To access the "Test screen" command, right-click in the project screen editor.) See also item 5186.
5186 Issue Resolved an issue where the "Test Screen" command would change the size of some screen objects that have the Position/Visibility animation applied to them. (To access the "Test screen" command, right-click in the project screen editor.) See also item 5185.
5208 Issue Modified the OPC UA Client and OPC XML/DA Client tasks to set tag quality to BAD when the connection to the OPC Server is lost.
5210 Issue Resolved an issue where the project security system did not verify that a client request had been processed before the next request was sent. This sometimes caused the project to become unstable, when the client received responses to requests that had timed out.
5247 Issue Modified both the History-to-Text utility (HST2TXT.exe) and the built-in function Hst2Txt to improve their handling of Daylight Saving Time (DST).
5292 Issue Resolved an issue that was causing project file tagl.txt to be deleted under certain circumstances.
5313 Issue Resolved an issue with the "Built-in Dialogs Scale" setting (Project Settings > Web) where if it was set to anything other than 100%, it caused the "User Name" combo box in the "Log On" dialog box to be displayed incorrectly.
5330 Issue Resolved an issue where an incorrect message was displayed when the project developer tried to insert the same System Symbol more than once.
5351 Issue Resolved an issue where the built-in function GetOS would return incorrect values when called on Windows Embedded Standard.
5377 Issue Resolved an issue with the built-in functions PrintWindow and SaveScreenshot where, if the functions were used to print or save a closed screen that contained a Trend Control object, the object was not printed or saved correctly.
5378 Issue Resolved an issue where the run-time user could accidentally close the viewer on Windows Embedded if they clicked or tapped the top-right corner of the project screen.
5392 Issue Resolved an issue where a screen file sometimes became corrupted if the project developer deleted an ActiveX control from the screen and then saved it.
5455 Issue Resolved an issue with the Grid Control object where if it was configured to use Class Tag as its data source, it would show BAD quality for the wrong array elements.
5616 Issue Modified the Protection Manager to allow you to select a MAC address when you change your softkey license. This is necessary because the license's site code is based on the computer's MAC address, and the computer may have more than one MAC address if it is connected to a VPN or otherwise using a virtual NIC at the time that you change your license.
5634 Issue Implemented safeguards to prevent memory overflow errors that sometimes occurred when using TreeView Control (TreeView.ocx) in a project screen.
5804 Issue Resolved issue with Remote Management experiencing timeout problems when downloading projects to remote computers when the Remote Agent is configured with users and passwords on its Security System
5884 Issue Resolved an issue where the built-in function TagsDBAddTag would not accept new tag names beginning with the "@" character.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 1 (Friday, July 04, 2014)

ID Type Description
4864 Change Request Enhanced Studio Mobile Access (SMA) messages to precisely indicate when compression is enabled (unsupported) or when the screen is not published. Also added instructions to the error message explaining how to open the browser console to get additional information.
3649 Issue Modified the Studio Mobile Access (SMA) Thin Client interface to support connection to the server through routers.
3929 Issue Modified the Alarm/Event Control object to sort messages properly by Date/Time, even when the historical data is saved in an external database.
4349 Issue Modified the label ""Extern Translation"" to ""Enable Translation"" on the ""Object Properties > Messages"" dialog of the Smart Message object (on the development environment) for consistency.
4374 Issue Resolved issue with a form being displayed by the Studio Service Tray in some systems
4386 Issue Modified the graphic interface to support data entry for objects with mnemonics even when the ""Use popup input for text objects"" option from Project >> Settings >> Viewer is enabled (checked).
4426 Issue Modified the Driver task to support writing floating point (real) values with precision beyond the 6th decimal digit for drivers that handle real values as string
4509 Issue Resolved issue with the Text Object alignment of text being ignored when using the translation tool to switch to a different language during the runtime
4557 Issue Modified the Collaboration Server to make sure that the tags database main file (Tagl.txt) is converted to XML format when applicable, in order to avoid errors.
4585 Issue Modified the Tag Integration for the ""AutomationDirect Koyo"" provider to support CSV files with ""unassigned items"".
4680 Issue Modified the OPC DA/XML task to recognize the data type of items that were not ""available"" for the OPC Server when the OPC DA/XML Client task was launched, but eventually become ""available"" (e.g.: connect the device to the network only after the OPC DA/XML task was launched). The new algorithm allows the OPC DA/XML Client to recognize the data type of items that become available during the runtime and, consequently, be able to write values to such items.
4681 Issue Improved the performance of the Tag Integration for the ""RSLogix 5000 family"" provider when loading tag names from the L5K file. Moreover, the Tag Integration was modified to ignore ""Encoded Data blocks"" while importing the remaining tags available in the L5K file.
4728 Issue Modified the Trend Task to avoid missing samples when the format of the Trend worksheet(s) was set to Proprietary (*.hst files).
4752 Issue Modified the OPC XML/DA Client task to indicate bad quality for the tag(s), if any, associated with a blank or invalid item, while communicating properly with the remaining items properly configured in the same OPC XML/DA Client worksheet.
4753 Issue Modified the OPC XML/DA Client task to recognize changes implemented in the OPC XML/DA Client worksheets and saved while the task was running - online configuration.
4766 Issue Modified the TCP/IP Server to handle legacy alarm controls asynchronously, preventing possible system errors
4770 Issue Modified the Collaboration server to prevent it from displaying error messages when editing tags in a project without any classes (Project Explorer > Global > Classes).
4843 Issue Modified the ImportXML built-in function to handle the size (height and width) of polygons properly and avoid settings unexpected values for the object width when editing it with the development environment (screen editor) after importing the screen(s).
4890 Issue Resolved issue with the tag quality remaining Uncertain after the user attempted to enter values out of the configured min and max range
4942 Issue Resolved an issue with the alignment of Text objects in the screen worksheet, when the Text Data Link animation was applied to the objects and the Auto Size option was enabled.
5081 Issue Corrected the Studio Mobile Access log system that was reporting a wrong line number when a script had a VBScript code line break (""_"" character) inside a VBScript comment.
5101 Issue Modified the Trend Control to display the pens in Online Mode, even if the values are saved in an external database with TimeStamp set to Local Time (not UTC).
5116 Issue Resolved issue with disabling all objects that can receive focus in a screen during the runtime could cause unstable behaviors
5181 Issue Update OPC OpenSSL to the latest version to address CCIRC Advisory AV14-031 OpenSSL vulnerability
5184 Issue Modified the Trend/Alarm database interface to prevent 100% CPU usage when inserting data on relational databases
5197 Issue Modified the asynchronous database insertion algorithms to prevent instability that could cause system errors
5213 Issue Improved the Studio Mobile Access (SMA) script error information to allow better identification of the script that is preventing the screen from opening.
5215 Issue Improved the Studio Mobile Access to support the VBScript code ""If $Tag Then $Function() Else $Function() End If"" all in the same line.

InTouch Machine Editionv7.1 + Service Pack 3 + Patch 6 - Known Issues (Friday, June 26, 2015)

ID Type Description
1748 Issue Import Wizard does not import Opc Ua, Opc Xi and Tag Integration configuration files [WORKAROUND]: Copy the Opc Ua, Opc Xi, and Tag Integration settings manually from the source project.
2033 Issue CEServer for EmbeddedView v7.0 does not properly handle when there is a MAC ID in the Registry [WORKAROUND]: The workaround is to manually clear the following registry key: This is the Registry Key: SYSTEM\\CurrentControlSet\\Control\\Class\\{4D36E972-E325-11CE-BFC1-08002bE10318}
2134 Issue Validation of the Custom Resolution fields happen when creating new projects even if you have selected one of the pre-defined resolutions [WORKAROUND]: Change the resolution back to Custom and write a value between 240 and 10000 on both fields. Then, choose one of the pre-defined resolutions on the Combo box
2534 Issue The Mobile Access legend is not properly redrawn on some specific conditions [WORKAROUND]: Toggle the cursor to for the legend redraw
4821 Issue If you modify a tag field that applies to the entire array Mobile Access will not synchronize the value to all the array elements [WORKAROUND]: Because the field has the same value for all indexes, you should use one index for all the locations where you need the field.